Product Overview
Product Description
| Product Series | Compact |
|---|---|
| product name | ComPact NSX |
| Product Series | ComPact NSX100...250 |
| product short name | NSX160F |
| product type | Breaker |
| Applications | Power distribution protection |
| Number of poles | 3P |
| Protection pole description | 3t |
| Rated current [In] | 160 A at 40 °C |
| Rated working voltage [Ue] | 690 V AC 50/60 Hz |
| Network Type | AC |
| Network frequency | 50/60Hz |
| Isolation function | Applies to EN/IEC 60947-2 |
| use category | Class AC |
| [Icu] rated ultimate short-circuit breaking capacity | 10 kA at 600 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| performance level | F 36 kA 415 V AC |
| trip unit name | TM-D |
| trip unit type | Thermomagnetic |
| Release protection function | LI |
| control type | Handle |
| Circuit breaker mounting mode | Stationary |